ThermonPrimaryLogo_2017.svg

566 - Base Load Step Control Step Control

The Caloritech™ 566 Base Load Step Control is made up of a mother board and 1 to 5 output boards, each with 4 outputs, for a maximum of 20 stages. Time delay between stages is independently adjustable for up and down sequencing from 1 to 200 seconds per stage. This step control can operate in base load control mode by receiving a signal from an SCR. It can also operate in standard step control mode receiving process signals directly from a control.

Features

  • Up to 5 output boards each with 4 outputs for a maximum of 20 stages
  • Independently adjustable time delay between stages from 1 to 200 seconds
  • Able to operate in base load control mode with signal from SSR or in standard step control mode with signals directly from a control

Specifications

4, 8, 12, 16 or 20 stages available
0/10V (SCR), 4-20 mA or 0-135 Ω input signal
24-120 VAC, 2 Amp Max. per stage SSR output
120 VAC power